Thanks to the built-in RF wireless sensor, the motion detected by one luminaire (the master LED) can pass onto the other pre-defined luminaires (the slave LED) through RF transmission. Easy to set up by either the rotary coding switch or remote controller, and up to 16 different groups can be created. |
Features & Benefits ● Detection range (diameter x height): Max. 12m x 6m ● Wireless communication between luminaires, no control cables needed. Transmission range can be 30 meters in door and 100 meters in open area. ● Up to 16 groups can be created. ● Selectable hold-time, sensitivity, daylight sensor, stand-by time and stand-by dimming level. | Dectection Pattern |
While the 1st sensor detects motion on the 1st floor, it switches the light on 100% and sends signal to all slave units. All slaves on the 1st floor turn on 100% and the master on the 2nd floor goes to stand-by level. | The person walks to the 2nd floor, the 2nd master switches the light on 100%. All slaves on the 2nd floor turn the light on 100% and the master on the 3rd floor goes to stand-by level. | |
When walks to the 3rd floor, the 3rd master switches the light on 100%. All slaves on the 3rd floor turn the light on 100% and the master on the 4th floor goes to stand-by level. Meanwhile, the lights on the 1st floor are dimmed to stand-by level after hold-time. | The person walks to the 4th floor, the 4th master switches the light on 100%. All slaves on the 4th floor turn the light on 100% and the next master goes to stand-by level. Meanwhile, all sensor on the 1st floor turn the light off after stand-by period, and all lights on the 2nd floor dim to stand-by level after hold-time. |
Sensitivity Detection area can be adjusted by selecting the combination on the DIP switches to suit each application. Sensitivity Option: 100% / 75% / 50% / 25% /10% | |
Daylight Threshold The daylight threshold can be set on DIP switches to suit each application. Daylight Sensor Options: 2Lux / 10Lux / 50Lux / Disable | |
Hold-time Hold-time is the period the lamp stays on 100% after the person has left the detection area. Hold-time Options: 5s / 30s / 1min / 5min / 10min / 20min / 30min | |
Stand-by Period (Corridor Function) This is the time period required at the low light level before it is switched off after the absence of people. Stand-by period options: 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞ * Set stand-by time at infinity for bi-level control. | |
Stand-by Dimming Level This is the dimmed low light output level you would like to have after the hold-time in the absence of people. Stand-by dimming level options: 10% / 20% / 30% / 50% | |